Entry description:
Access Read only
PDO mapping No
Value range UNSIGNED32
Default value 0x191
Object 0x1001: Error register
This object is an error register for the device.
Object description:
Index 1001h
Name Error register
Object code VAR
Data type UNSIGNED8
Category Mandatory
Entry description:
Access Read only
PDO mapping No
Value range UNSIGNED8
Default value 0
Data description (M for Mandatory and O for Optional):
Bit M/O Meaning
0 M Generic error
1 O Current
2 O Voltage
3 O Temperature
4 O Communication error (overrun, error state)
5 O Device profile specific
6 O Reserved (always 0)
7 O Manufacturer specific
If a bit is set to 1, the specified error has occurred. The only mandatory error that
must be signaled is the generic error, which is signaled in any error situation.